15 T/H Oil Fired Steam Boiler Technical Parameters
Performance and efficiency
- Boiler Load: 100%
- Total steam production: 15,000 kg / h
- Maximum operating pressure - PMO: 25.0 bar (g)
- Maximum allowable working pressure - MAWP: 27.2 bar (g)
- Test hydrostatic pressure: 40.8 bar (g)
- Superheated steam temperature: 360 ° C
-Temperature Of water supply: 105 ° C
- Temperature of gases in the furnace outlet: 610 ° C
-Temperature gas in the boiler output: 345 ° C
- Temperature of gases in the superheater outlet: 629 ° C
- Temperature of gases in the economizer outlet: 230 ° C
- Temperature of the gases at the exit of the air preheater 160 ° C
- Combustion air temperature: 130 ° C
- Excess air: 60%
- Thermal Furnace Release: 11,627,832 kcal / h
- Fuel: Chopped wood
- Maximum humidity Fuel: 55%
- PCI - lower heating value fuel power: 1,750 kcal / kg
- PCS - high calorific fuel power: 4,670 kcal / kg
- Fuel consumption: 6644 kg / h
- Combustion air flow rate: 31,861 kg / h
- Flue gas flow rate: 41,240 kg / h
- Efficiency (PCI): 83.3%
15 T/H Oil Fired Steam Boiler
Load losses - gases
- Furnace: 25 mmH2O
- Steam pipe: 60 mmH2O
- Superheater: 25 mmH2O
- Saver: 50 mmH2O
- Pre-heater: 25 mmH2O
- Multicyclone filter: 90 mmH2O
- Pipelines and chimney: 45 mmH2O
- Damper: 10 mmH2O
- Total: 330 mmH2O
Load losses - Air
- Grid: 30 mmH2O
- Pipelines: 30 mmH2O
- Air preheater: 60 mmH2O
- Total: 120 mmH2O