25 Tph High Temperature CFB Steam Boiler Technical Parameters and Installation Requirements

Model

Capacity

Application

case case case

 2. The boiler plant consists of the following equipment:

- steam boiler E 25-39-440 with a furnace of high-temperature fluidized bed (WTCS);

- Economizer

25 Tph High Temperature CFB Steam Boiler

25 Tph High Temperature CFB Steam Boiler

2.1. The basic technical characteristics and requirements for the CFB steam boiler:

Name of parameters

Unit

Value

Fuel - middlings (by-product coal)

-

-

boiler steaming capacity

T/h

25

Steam pressure at the steam superheater outlet (excessive pressure)

MPa

3,9

Superheated steam temperature

°С

440

Feedwater temperature

°С

145

Slag dust removal – dry

 

 

2.2 Technical characteristics of fuel:

Name of parameters

Unit

Value

operating humidity

%

10-15

Ash content in as-received basis

%

35-45

Devolatilization in as-received basis

%

20-25

low heat value

Kcal / kg

3000-4500

high heat value

Kcal / kg

7800-8300

3. General requirements for boiler installation

3.1 Ensure a stable burning of fuel in the boiler plant furnace.

3.1.1. Ensure boiler plant operation on the middlings with the following steam parameters:

  • - absolute pressure 3,9 MPa;
  • - temperature 440 0С;
  • - Steam capacity 25 t/h

3.2. Provide steam capacity of the boiler in the control range from 30 to 110% of the rated load.

3.3. The boiler plant must comply with the requirements of this technical specification.

3.4. All delivered equipment must have certificates of conformity, the necessary marking, passports, instructions for installation and operation, the corresponding results of control.

3.5. The quality of the steam according to its content must comply with the requirements of normative technical documentation for power plants of medium parameters (GOST 20995-75).

3.6. The boiler installation should be provided with thermal insulation with a protective layer so that the surface temperature of the heated and heating elements of the equipment does not exceed 450 ° C.

If you have any questions, please contact our Executive Manager and we will get back to you as soon as possible

RELEVANT CASES

RELEVANT PRODUCTS

Get An Instant Quotation

For all inquiries, please fill in the form below (* are required) to send us a brief message, and we will get back to you as soon as possible.


HOW TO CONTACT

Chat Online

If you are interested in our products, please feel free to contact us now! Click and chat online.

chatOnline
  • Heat Converters
  • Pressure Converters
  • Temperature Converters

Any question, please contact us for free. Phone number: +86-371-86686767 Skype: zgboiler Email:zbgboiler@zzboiler.com

KW
bar
    °C