What should notice during the construction of gas fired boiler room
Due to the gas fired boiler belongs to special equipment,natural gas belongs to combustible and explosive fuel,we should pay attention to some problems during the construction of gas fired boiler room.Zhengzhou Boiler Co., Ltd.,as an experienced industrial boiler manufacturer in China,gives the following problems needing our attention:
The safe distance between gas fired boiler and buildings
The distance between the gas fired boiler and the building should meet the needs of the operation,maintenance and layout of ancillary facilities,and should not be less than 3.0m for the 1 ~ 4 t/h gas steam boiler and 0.7~2.8MW gas hot water boiler,4.0m for the 6~20t/h gas steam boiler and 4.2~14MW gas hot water boiler,5.0m for the 35~65t/h gas steam boiler and 29~58MW gas hot water boiler.
The safety measures of gas fired boiler room
The air channels of appropriate size should be provided to ensure the proper air for combustion and air conditioning.In general,there should be two air channels for the air exchange with the air outside the gas fired boiler room.
There should not be negative pressure in gas fired boiler room.If the automatic combustion air damper is installed,it must implement the interlock with the burner of gas fired boiler to ensure that the burner will no longer work once the damper is closed.